Guided exploration of a winter air conditioning cycle

Air conditioning of a bank, located in a cold and humid place

Introduction

The objective of this guided exploration is to guide you through your first steps in using Thermoptim to study a building air conditioning cycle.

The software package has indeed the functions allowing moist gas calculations to be carried out.

The case most often encountered in practice is obviously that of humid air at atmospheric pressure, and Thermoptim allows many air conditioning problems to be solved. But, more generally, it makes it possible to study moist gases of any composition.
Note however that the air conditioning calculation functions in Thermoptim do not have a graphic representation in the diagram editor. Calculations are carried out in processes of a particular type as well as in a specific mixer.

These processes all model changes undergone by the humid air, with the exception of the determination of the supply conditions, which, although carried out in a process, simply corresponds to the calculation of the state to be obtained at the end of the air treatment.

Another particularity is that the flow rates are related to dry air.

In this guided exploration, we offer you the following steps:

Presentation of the problem

Objectives pursued

The installation that we are going to study corresponds to a bank, located in a cold and humid place, which we want to air-condition.

We try to maintain the interior atmosphere of the building at a temperature of 20 ° C and a relative humidity equal to 30%.

The external climatic conditions are as follows: temperature equal to - 10 ° C and relative humidity of 90%.

It is necessary to provide a thermal input with a power of 100 kW excluding air renewal, but no water. To avoid any parasitic condensation, the fresh air is preheated to 10 ° C.

Principle of air treatment

For this, we have a ventilation circuit that allows air to be blown in different places of the building.

For hygienic reasons, it is necessary to renew the air, but a part can however be recycled, which makes it possible to reduce the need for air conditioning.

Part of the interior air is therefore recycled, which is mixed with exterior air, previously preheated to avoid any risk of condensation on the ducts or of the registers seizing up.

This mixture must be treated before being injected into the ventilation circuit, so that its state corresponds to the blowing conditions.


These are calculated in such a way that the required heat input is provided, as well as the amount of water to achieve the desired relative humidity. In addition, for reasons of comfort, the supply temperature must not be higher than a certain value which is set here at 27 ° C.

It is also assumed that the supply fan heats the air by 1 ° C.

A possible treatment of the mixed air consists of humidifying it adiabatically until the specific humidity corresponding to the desired supply conditions is obtained, then heating it up to the supply temperature. There are others, but this is the one that will be presented here.

Detailed resolution

Loading the model is done by opening the diagram file and a properly configured project file.

Start by loading the model, then complete the other suggested activities.

Load the model

Click on the following link: Open a file in Thermoptim

You can also:

  • either open the "Project files/Example catalog" (CtrlE) and select model m12.2 in Chapter 12 model list.
  • or directly open the project file (aircond_Winter.prj) using the “Project files/Load a project” menu in the simulator menu.

    There is no need to open a diagram file because there is none for moist processes.

Determination of supply conditions

Let us start by studying the preheating of the outside air.

It is modeled by a moist type heating process.

The upstream and downstream points of this process have the settings below. Remember that, to obtain these results, you must open the upstream point by double-clicking on its row in the simulator points table, then that you must click on the "Water vapor/gas mixtures" tab and click on the button "set w", because, when Thermoptim is opened, these calculations are not yet carried out.

To be able to determine the supply conditions, it is necessary, as shown in the diagram of the treatment system, to mix the preheated outside air and part of the recycled inside air.


Remember that the outside air has a relative humidity epsilon of 90% and a temperature of -10 ° C.

This mixture is modeled using a moist mixer which receives as input a process-point representing the recycled air, and the “preheating” moist process.

Open this mixer by double-clicking on the row of the node table located at the bottom left of the simulator screen.

The setting of the point making it possible to determine the state of the indoor air is given opposite. It has a relative humidity epsilon of 30% and a temperature of 20 ° C.

We have entered as flow rate in the mixer inlet process the value of 0.7, so that the proportion of recirculated air is equal to the limit value of 70% indicated above.

Calculate the moist mixer, then open the "mixed air" point.


Its temperature is 17 ° C and its humidity w is equal to 0.0346 kg of water per kg of dry air.

Now that we know its properties, we can determine the supply conditions.

A specialized design office has previously determined the internal and external thermal inputs that must be removed. They correspond to a power of 100 kW.

Open the supply process by double-clicking on its row in the process table.

You will find this value in the "thermal load" field located in the center of the screen, positively because it is a power to be supplied to the building.

To set up the calculation, we set the supply temperature at 27 ° C by entering this value in the downstream point and calculating it.


We have also entered a very low value for the water load, to avoid divisions by 0 and the resulting display problems.

When the supply process is calculated, it determines on the one hand the humidity of this point, which is the same as that of the indoor air because there is no water load, and on the other hand the flow of dry gas necessary to compensate for the thermal load.

The problem now is how to treat the mixed air (17 ° C, w = 0.00346) to obtain the supply conditions (27 ° C, w = 0.004334).

As we said, one solution is to humidify it until its specific humidity is equal to that of the supply air, then reheat it to achieve the desired temperature.

Calculation of the adiabatic humidifier

In the downstream "humidified air" point, we start by entering w = 0.004334 as the specific humidity.


The only parameter setting of the "humidifier" moist process is the choice of the calculation mode, here "Calculate the process, the downstream point being known".

The process can be calculated.

We obtain the following results: the temperature of the humidified air is equal to 14.81 ° C, and the effectiveness of the humidifier is 25.7%.

Remember that adiabatic humidification is obtained by spraying water to form a rain which sprinkles the air, the heat input necessary for the vaporization of the water being provided by the air. Like what is done for the cooling of a moist mixture, the reference is a theoretical humidification leading the air to saturation, the real humidification being characterized by its effectiveness epsilon.

Calculation of the heating process

Now that the humidified mixture is at the correct humidity, it suffices to reheat it slightly to obtain the desired supply conditions.


To determine the temperature rise to be provided, open the "heating" moist process connecting the "humidified air" point and the "supply" point. Its flow rate is the same as that of the "supply" and "humidifier" processes.

Its only setting is the choice of the calculation mode, here "Calculate the process, the downstream point being known".

Plot of the cycle in the psychrometric chart

First step: loading the psychrometric chart

We will now study the cycle in the psychrometric chart.

Click this button

You can also open the chart using the line “Interactive Charts” of the “Special” menu of the simulator screen, which opens an interface that links the simulator and the chart. Double-click in the field located at the top left of this interface to choose the type of chart desired (here “Psychrometric”).

Once the chart is open, select “(w, t)” in the “Chart” menu, and click on the line “Load a base gas” in the Gas Editor menu, and choose “air” among the Protected compound gases.

If the window is displayed correctly, but without showing the iso-value lines of the chart, it is undoubtedly that the display interval of the values ​​is not the right one, because of previous settings.

It is possible to modify the calculation and display values ​​by adjusting the parameters in the chart menus:

  •     Open the Chart/ X Axis menu line, then enter a minimum of -15 and a maximum of 35 to define the temperature values ​​to be displayed
  •     Open the Chart/ Y Axis menu line, then enter a minimum of 0 and a maximum of 0.005 to set specific humidity values ​​to display
  •     If the iso-values ​​lines are not the correct ones, open the Graph / parameters menu line, then enter the following values ​​to define the iso-values ​​to display:
    • Dry temperature between -15° C and 35°C
    • Pressure 1.01325 bar

Second step: loading a pre-recorded cycle corresponding to the loaded project

You can open this cycle as follows: in the chart window, choose “Load a cycle” from the Cycle menu, and select “climEte_Fr.txt” from the list of available cycles. Then click on the “Connected points” line of the Cycle menu.

This image calls for several comments.

The air treatment cycle is shown in the chart, with the mixed air properly located on the mixing line which connects the indoor and outdoor air.

Cooling with a drop in the specific humidity of the air is represented by the line which connects the mixed air to the cooled air, the leftmost point of the cycle.

Finally, heating at constant specific humidity corresponds to the small horizontal line segment in the lower part of the cycle, on the left, which ends at the "supply" point.

Appendix: moist gases in Thermoptim

General principles

A moist gas can be represented in THERMOPTIM in two equivalent ways: either directly as a compound substance comprising at least two constituents: H2O and another gas, pure or compound, or as a dry gas for which we know the specific humidity.

The first way has the advantage that the composition of the moist gas is accessible at all times. On the other hand, it assumes that, for the same dry gas, a new moist substance is created for each value of the relative humidity.
The second representation is much more concise, since it only uses the invariant gas and the value of the specific humidity.

Calculation of the properties of a point represented by a moist gas

The "Water vapor/gasmixtures" tab of the points screen allows you to calculate the properties of moist gases.


When the gas is represented by a moist substance , the latter may have been mixed in a mixer, generated from a dry gas and a specific humidity, or even defined directly by the user, in which case care should be taken that water has been defined as gas (H2O). Let us, for example, consider humid air, the composition of which is as follows:

Construct a point using this substance , at the pressure of 1 atmosphere and the temperature of 35 ° C, and click on the tab titled "Water vapor/gasmixtures". The following screen appears:

On the left appear the data relating to the point considered: specific humidity w, relative humidity epsi. On the right are indicated the specific values ​​(that is to say related to 1 kg of dry gas) of the enthalpy, the volume, as well as the moist bulb temperature and dew point temperature. Any condensate is displayed on the left below the relative humidity.

Calculation of moist characteristics

To calculate all the moist characteristics of the point, click on the "set w" button. The following results are displayed:

Setting relative humidity

It is also possible to set a particular value of the relative humidity, by entering this value in the corresponding field, then by clicking on the button "set epsi". Suppose we set a relative humidity equal to 0.5:

It is possible to modify the water content of the moist gas by clicking on the button "set the humidity of the gas". The composition of the gas is here modified as follows:

Calculation of the properties of a point represented by a dry gas

The composition of the dry gas being most often invariant, we have seen that it is interesting to define a moist gas by referring to its dry gas. As a departure from the general rule used in the software package, THERMOPTIM allows this to be done by constructing points defined by the dry gas and the value of the specific humidity.

By way of example, thus construct a point of pressure 1 atmosphere and temperature 35 ° C, associated with the substance  "atmospheric air", then click on the "Water vapor/gasmixtures" tab, and set as before a relative humidity equal to 0.5. The result you get is the following, identical to the previous one except for rounding:

Moist process screens

To study the changes that a moist gas can undergo, a "moist" process has been introduced. In fact, it corresponds to six different processes, which are distinguished by their category. The screens of the moist processes look like this, but they vary slightly depending on the category chosen:

This is a "supply" moist process, making it possible to calculate the supply conditions to maintain a desired environment, taking into account the given water and thermal loads.


Before detailing how to use this screen, let us specify a few points which apply to all moist processes.

First of all, THERMOPTIM only performs process calculations between moist points insofar as these points are represented by their dry gas and their humidity. The reason is simple: this mode of representation avoids having to introduce a new moist substance  for each value of the humidity.

It should be noted that this way of doing things is quite exceptional in THERMOPTIM: for all the other processes, the calculations are made from the precise composition of the substance  considered. If therefore couplings have to be made between moist processes and other processes, care must be taken to interconnect them by moist substances.

Moreover, the quantities being preferably expressed in specific units, the flow rates which appear on the processes are the dry gas flow rates.


The notion of effectiveness is often used to qualify real processes compared to theoretical or ideal processes. In practice, the latter generally correspond to evolutions whose final state is saturated (complete humidification, cooling to saturation).

The upper right part of the screen recalls the general characteristics of the process, while the left part displays the upstream and downstream points, with indication of their temperatures, pressure, specific enthalpy and specific humidity.

The settings for the different categories of moist processes, and the calculation options are located in the central and lower right area.

Supply process

This process connects the point describing the known indoor environment (upstream point) to the point corresponding to the desired supply conditions (downstream point).

The fields to the right of the screen are used to enter the water and heat loads to be discharged, in kg / s and kW respectively. It is assumed that the water load must be discharged at the temperature of the indoor point.

Thermoptim then calculates the values ​​on the one hand of the "slope ratio gamma", which represents the ratio between the variations of specific enthalpy and humidity, and on the other hand of the total enthalpy Delta Q' involved in the process (on the basis of specific enthalpies).


Two actions are possible here:

Cooling process

This process makes it possible to study the cooling of a humid gas on a cold coil, with or without condensation.

The cooling conditions are specified on the right of the screen: surface temperature and cold coil effectiveness, if they are both known. If the effectiveness is not known, we can calculate the process given the humidity of the downstream point.


Two actions are possible here:

Water / steam or adiabatic humidification process

These two types of processes make it possible to study either humidification with water or steam, or adiabatic humidification.

The humidification conditions are specified on the right of the screen: water or steam temperature and pressure, and humidifier effectiveness, if known.  If the effectiveness is not known, we can calculate the process given the humidity of the downstream point.

Two actions are possible here:

Heating process

This process makes it possible to carry out various calculations of changes undergone by a moist gas. Depending on the case, the water content of the two points may be the same or different.

Two actions are possible here:

Dessication process

This process makes it possible to study dehumidification by desiccation or the regeneration of a desiccant.

Different types of desiccant materials are available, their name and heat of sorption being displayed on the right of the screen, the latter can be modified if the user wishes.

Two actions are possible here:
Note that the same process calculates both the desiccation and the regeneration of the desiccant, according to the relative values ​​of the upstream and downstream points. For regeneration, however, the software does not check whether the temperature is sufficient.

Moist mixer

This node is used to determine the moist properties of a mixture of several dry moist gases.

A moist mixer differs from a simple mixer in the following ways:

Usually the downstream point is on the mixing line. In the event of oversaturation, a message informs the user and Thermoptim searches for the mixing point on the saturation curve, while ensuring the conservation of the enthalpy. The excess water is then displayed above the branch table.

The values displayed are not expressed in relation to dry gas.